3:51 video: who's taking the memory, the two past memory-fab outages, and voltage sags, which are more common than outages.
4:42 English-language video: the memory shortage, the two past memory-fab outages, and voltage sags, which are more common than outages.
Summary: during a memory shortage, which power problem should factories guard against most?
When memory supply is tight, every line stoppage costs capacity that could have been sold. Long outages have precedent. In March 2018, a roughly half-hour outage at Samsung's Pyeongtaek fab reportedly damaged about 60,000 NAND wafers (about 3.5% of that month's global NAND wafer output). In June 2019, a 13-minute outage in Yokkaichi, Japan, affected about 6 EB of NAND supply by Western Digital's estimate. But what factories run into more often is a voltage sag, usually lasting less than a second. Power isn't cut, yet a tool's control power can still reset, and Southern Taiwan Science Park saw 13 sags in 2020 alone. UPS and generators handle long outages. For sags under 3 seconds, a Voltage Sag Protector (VSP) can protect just the control circuits that would reset.
Why is iPhone 18 hard to buy? AI has taken the memory
iPhone 18 Pro starts at NT$44,900 in Taiwan, NT$5,000 more than the previous generation (TechNews). Part of the reason is memory. Think of a memory fab as a kitchen: AI data centers order high-bandwidth memory (HBM), which is highly profitable, so naturally the kitchen makes that first. The standard memory that phones and PCs need has to wait in line.
Memory makers are all building new fabs, but most won't reach volume production until next year or later. Nikkei Asia estimates that memory output must grow about 12% a year to keep up with demand, while Counterpoint notes that current expansion plans add only about 7.5% a year (as cited by Lowyat.NET). New fabs can't catch up, so existing fabs are left with one job: the lines can't stop.
Memory fabs have lost power before: how much supply did two long outages cost?

To be clear, this year's iPhone shortage wasn't caused by an outage. But the two past cases show what happens when a line stops.
| Event | Outage duration | Impact |
|---|---|---|
| March 2018, Samsung Pyeongtaek fab | About 30 minutes | About 60,000 NAND wafers reportedly damaged, about 3.5% of that month's global NAND wafer output |
| June 2019, Yokkaichi, Japan | 13 minutes | Western Digital estimated about 6 EB of NAND supply was affected; at 256 GB per phone, that's the storage of about 23 million iPhones |
Samsung's figure comes from media reports at the time (Lowyat.NET). The 6 EB for Yokkaichi is Western Digital's own estimate, and the iPhone count is our conversion at 256 GB (bit-tech). When memory is already short, another outage would only widen the gap.
More common than outages: voltage sags lasting under a second
To be fair, both cases above were long outages, which are a job for UPS and generators. What factories run into more often is a voltage sag, usually lasting less than a second. Power isn't cut, but the tool's PLC or control power supply may reset first and the tool stops. Then it has to be restarted, inspected and re-qualified. For how voltage sags differ from outages, see What is a voltage sag.
- 2020, Southern Taiwan Science Park→According to Taipower, 13 voltage sags occurred in a single year (Commercial Times)
- June 1, 2023, Southern Taiwan Science Park→A Taipower substation equipment fault caused voltage sags at some companies in the Tainan and Kaohsiung parks. UMC confirmed that some wafers were scrapped and some tools had to be restarted, with losses still being tallied (CNA)
Losses from such events are rarely disclosed. Normally, capacity lost to tool trips can be made up with overtime, but during a shortage, every restart is capacity you can't sell.
Why do tools still trip after passing SEMI F47?
Semiconductor tools have a voltage sag immunity standard called SEMI F47. Yet SEMI's Voltage Sag Immunity Task Force held its October 2025 workshop specifically to discuss “why tools remain susceptible to voltage sags even after F47 was implemented.” It proposed that the next revision prioritize test waveforms closer to real-world sags (SEMI Standards Watch, 2025-12).
Another common reason is that F47 covers the main equipment, while control power supplies, contactors and industrial PCs added to the tool later aren't necessarily within the test scope. For how to harden older or modified tools, see How to improve legacy equipment that doesn't pass SEMI F47.
Our recommended approach: protect only the control circuits that reset
Our recommended approach is the Voltage Sag Protector (VSP). You don't need to protect the whole tool, only the control circuits that would make it reset. When it detects a sag, it switches to supercapacitor power within 1 ms and rides through up to 3 seconds at full load.
| Condition | Duration | What to do |
|---|---|---|
| Voltage sag | Usually under 1 second | VSP protects control circuits, up to 3 seconds at full load |
| Short outage | Seconds to minutes | UPS |
| Long outage | Minutes or longer | UPS bridging to generator |
VSP isn't meant to ride through outages. It can't cover an outage longer than 3 seconds, but sags of a few hundred milliseconds are exactly its range, and the two can coexist. To size it, follow the 5 steps in How to size a voltage sag protector.
FAQ
What does the iPhone 18 shortage have to do with memory?
AI data centers are buying high-bandwidth memory in bulk, so memory makers prioritize these higher-margin products and supply of the standard memory used in phones and PCs is tight. Most new fabs won't reach volume production until next year or later. This year's shortage wasn't caused by power outages.
How much can a power outage at a memory fab cost?
In 2018, a roughly half-hour outage at Samsung's Pyeongtaek fab reportedly damaged about 60,000 NAND wafers. In 2019, a 13-minute outage in Yokkaichi affected about 6 EB of NAND supply by Western Digital's estimate. Beyond scrapped WIP, the time spent restarting and inspecting is also lost.
What's the difference between a voltage sag and an outage?
In a voltage sag, power isn't cut. The voltage briefly drops to 10–90% of nominal, typically for about 0.1 seconds in Taiwan's science parks. An outage is an interruption of supply. Sags happen far more often, and a tool stops as soon as its control power resets. See What is a voltage sag.
Do you still need a voltage sag protector if you have a UPS?
They do different jobs. A UPS provides backup during outages. A voltage sag protector handles momentary sags of up to 3 seconds and protects only the control circuits, so it needs little capacity and has low standby losses. The two can coexist; choose based on the tool and budget.
Source
- TechNews, “iPhone 18 Pro and Pro Max Launch, with Taiwan Prices Up at Least NT$5,000,” 2026-09-10. Link
- Lowyat.NET (citing Nikkei Asia and Counterpoint), “Report: Memory Makers Only Expect To Meet 60% Of Demand By End 2027,” 2026-04-19. Link
- Lowyat.NET, “60,000 NAND Wafers Damaged At Samsung Plant Due To Power Outage,” 2018-03-15. Link
- bit-tech, “Power outage drops WD's flash output by six exabytes,” 2019-06-28. Link
- Commercial Times, “STSP Companies Complain of Frequent Power Problems... Taipower: Mostly Caused by External Factors,” 2021-04-16. Link
- CNA, “STSP Equipment Fault Causes Voltage Sag; UMC: Some Wafers Scrapped, Tools Restarted,” 2023-06-01. Link
- SEMI Standards Watch, “SEMI Voltage Sag Immunity Task Force Workshop Held at SEMICON West,” 2025-12. Link